Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T07CM01493
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/11/2007 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
04/11/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM01493 4/11/07 1. Indicate compliance with the Tucson Lighting Code, Section 7.1.2. If the fixtures are not full cutoff, Demonstrate uplight of less than 5% per 7.1.2 Paragraph 1, and document which Independent Testing Agency will field certify maximum aiming angle of 25 degrees per 7.1.2 Paragraph 2. |
07/24/2007 | GBONILL1 | ZONING | REVIEW | Needs Review | |
07/24/2007 | GBONILL1 | ENGINEERING | REVIEW | Needs Review | |
07/24/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/24/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |