Permit Number: T07CM01474
Parcel: 11917013D

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T07CM01474
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2008 BIANCA RAMIREZ ENGINEERING REVIEW Denied DATE: January 23, 2008
ACTIVITY NUMBER: T07CM01474
PROJECT NAME: Veterans Plaza
PROJECT ADDRESS: 3502 South 6th Avenue
PROJECT REVIEWER: Bianca Ramirez, CFM, Engineering Associate

The following items must be revised or added to the site plan.

Include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: SITE PLAN, DRAINAGE REPORT

SUBMITTAL REQUIRED: SOIL'S REPORT, GRADING PLAN

A grading review, approval and permit will be required based on the cut and fill quantities shown on sheet SI-9.

1. Provide future sight visibility triangles for the entrance/exit drive to 6th Avenue. The stem side is drawn from the future curb location. DS 2-02.2.1.A.10.

Revise existing SVT's with appropriate dimensions.

2. Provide finish grades on sheet SI-2. DS 2-02.2.1.A.16.

The above comment is from the previous review. It is acknowledged a note has been provided that references the grading plan sheet SI-9 for grading information. This is acceptable. However the provided contours do not match what is found on the Department of Transportation's Map Site.
Provide either an Alta Survey that supports the provided contours shown on SI-9 or revise the plan to show accurate contours. Be sure to provide the correct vertical datum.
Response letter not provided. Provide response letter explaining the reason for the discrepancy. Provide survey information along with supporting documentation signed and sealed by the appropriate professional.

3. Provide estimated cut and fill quantities on sheet SI-2. DS 2-02.2.1.A.17. 3rd request.

4. Per the Major Street and Route Plan 6th Avenue is designated for a future ROW width of 120'. Provide the 60' future ½ ROW dimension. Show the future curb and sidewalk location. For a ROW width of 120' a 9' sidewalk area is required. Revise appropriately. See zoning's comment.


The above comment is from the previous review and it appears it has not been addressed. The plans show a 40' existing and future ROW dimension. The future ½ ROW width is 60'. The ROW information on the plan is not correct. Revise accordingly. See Zoning's comment.

If 6th Avenue is fully expanded, which I believe that it may be. Provided letter from City of Tucson Department of Transportation with next submittal.

5. If applicable show all easements of record with recordation data on the site plan. DS 2-02.2.1.A.20.

The above comment is from the previous review and it is not clear if this comment has been addressed since a response letter was not submitted. If this comment is not applicable please indicate so in the response letter.


6. The plans indicate a 6' sidewalk within the ROW, however when reviewing the paving plan there is 10' sidewalk area with 10' of stamped concrete (brick pattern). Clarify and revise the plan accordingly. Provide response letter indicating how this was addressed.

DRAINAGE REPORT COMMENTS

1. Provided

2. Provided

3. Provided

4. Provided

5. The provided contours do not match what is found on the Department of Transportation's Map Site. Provide either an Alta Survey that supports the provided contours shown in the drainage report or revise to show accurate contours.

Response letter not provided. Provide response letter explaining the reason for the
discrepancy. Provide survey information along with supporting documentation
signed and sealed by the appropriate professional.
01/15/2008 PETER MCLAUGHLIN ZONING REVIEW Denied The MS&R plan shows 6th Avenue as a designated major street with a future right-of-way width of 120 feet. Revise the dimension of MS&R right-of-way on all site plan sheets and landscape plan sheets as necessary and provide a site plan and landscape plan showing how the site will meet code in the future when 6th Avenue widening takes place. Note that additional comments may be necessary once right-of-way dimensions are corrected and the future plans are submitted.
DS 2-02.2.1.A.19, LUC 2.8.3.5.F If a letter has been obtained from City Transportation stating otherwise please include a copy with the next submittal.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/30/2008 CPIERCE1 OUT TO CUSTOMER Completed
01/30/2008 SHANAE POWELL REJECT SHELF Completed