Permit Review Detail
Review Status: Completed
Review Details: SITE
Permit Number - T07CM01474
Review Name: SITE
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/26/2007 | DAVE MANN | FIRE | REVIEW | Approved | Show fire hydrant location. The hydrant or new hydrant must be within 300 feet of all portions of both buildings or sprinklers provided in the buildings. |
| 05/07/2007 | PETER MCLAUGHLIN | ZONING | REVIEW | Denied | 1) Correct the text overstrike on Sheet SI-2 where the 24 foot dimension is printed over the letters "PAAL". 2) The site is made up of two parcels which must be combined with a signed, notarized and recorded Covenant Regarding Development and Use of Real Property. This document is available at the zoning review counter, City of Tucson Development Services Department. 3) Continuous accessible pedestrian circulation is required between the sidewalk within the right-of-way and the buildings. Revise plan to show a continuous pedestrian circulation system. DS 2-02.2.1.A.12 DS 2-08.3.1 4) The class 2 bicycle parking should be evenly distributed and located within 50 feet of the main building entrances. Revise plan to distribute the 4 bicycle parking spaces evenly between the two proposed buildings, with two spaces provided near each building. DS 2-09.4.1 5) Add a north arrow to the site plan sheets as required. DS 2-02.2.1.A.1 6) Add a disabled vehicle parking calculation to the site plan detailing the number of spaces required and provided. DS 2-02.2.2.A.4 |
| 05/14/2007 | HEATHER THRALL | ZONING HC SITE | REVIEW | Denied | Please see Peter's comments in the zoning review section. |
| 05/15/2007 | ANDREW CONNOR | LANDSCAPE | REVIEW | Denied | 1. Provide North arrow on landscape plan. 2. Within a vehicular use area, one (1) canopy tree is required for each 10 motor vehicle parking spaces and every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk) per LUC 3.7.2.3.A.1. Additional trees are required. 3. Provide Planting Plan on landscape plan. The planting plan and layout calculations will include the following information: § Sizes of plants indicated in boxes, gallon cans § Both the proper and common name of each type of plant material. § Plant materials located within SVT's should consist of ground cover or low-growing vegetation of a species that will not grow higher than (30) inches. However, trees may be planted within SVT's provided that: A) The trunk caliper, at maturity, will not exceed twelve (12) inches in diameter; B) The lowest branch of any tree is at least six (6) feet above the grade of the street, and C) Trees are not planted in a line that could result in a solid wall effect when viewed from an angle. LUC 3.7.2.8 & DS 2-06. 4. Submit NPPO plan or Application for Exception; include acceptable documentation, which clearly indicates that the project will not impact Protected Native Plants. 5. Landscape plan shall include irrigation specification design and layout per DS 2-06.5.4.A & DS 2-06.5.4.B including source of irrigation, sleeves for driveways and sidewalks, locations of valves, low-flow bubblers or drip irrigation. 6. The site plan and landscape plan must show identical site layout to avoid conflict between the two plans. Ensure that all changes to the site plan are reflected on the landscape plan. 7. Additional comments may apply. |
| 05/15/2007 | ANDREW CONNOR | NPPO | REVIEW | Denied | Submit NPPO plan or Application for Exception; include acceptable documentation, which clearly indicates that the project will not impact Protected Native Plants. |
| 05/17/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Designing the site plumbing constitutes the practice of engineering. Provide plans sealed by an Arizona Registrant. Reference Arizona Revised Statutes 32-144, Board of Technical Registration Rules R4-30-304. 2. Provide the rim elevation of the next upstream sanitary manhole. Determine the need for a backwater valve per Section 710.1, UPC 2003. 3. Show the inverts and slope of the building sewer line on drawing. (Note: the minimum slope for a 4" building sewer is ¼" per foot. A minimum slope of 1/8" per foot may be used if it can be shown that it is impractical to obtain a slope of ¼" per foot. Reference Section 718.1, UPC 2003.) Reference Section 103.2.3, UPC 2003. 4. Clarify the nature of and the need for the specified 2-way cleanouts shown on drawing SI-9. Reference Sections 103.2.3 and 707.6, UPC 2003. 5. Provide backflow protection to isolate the irrigation system from the building water supply. Reference Section 603.4.6.1, UPC 2003. 6. Reduced pressure backflow prevention assemblies shall have a diameter at least equal to the diameter of the service connection or the service line at the point of connection. Reference Section 27-76 (b), COT Ordinance 9976, http://www.tucsonaz.gov/water/docs/backflow-ord.pdf |
| 05/21/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/22/2007 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |