Review Details: COMMERCIAL TI

Permit Number - T07CM01439
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/06/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) CLARIFY HOW WINDOWS WILL BE ATTACHED TO NEW FRAMING.

2) YOU MAY NOT ATTACH WALLS TO CEILING GRID, IT TAKES DROP CEILING OUT OF CODE COMPLIANCE.

3) CLARIFY WEIGHT OF ROLL UP DOOR AND HOW IT'S ATTCHED TO EXISTING BUILDING.
04/06/2007 RSHERRY1 WWM REVIEW Passed
04/06/2007 ANY ENGINEERING REVIEW Approved
04/06/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/06/2007 MARTIN BROWN FIRE REVIEW Approved
04/06/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that the proposed mechanical design conforms to the requirements of Chapter 8, IECC 2003.
04/06/2007 ROBERT SHERRY WATER REVIEW Approved
04/06/2007 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
04/09/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
04/09/2007 GBONILL1 ZONING REVIEW Needs Review