Permit Number: T07CM01438
Parcel: 119045540

Address:
230 W AJO WY

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM01438
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/06/2007 MARTIN BROWN FIRE REVIEW Approved
04/06/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide calculations to show that the ventilation for the new area complies with the requirements of section 403.3, IMC 2003.
04/06/2007 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
04/06/2007 ROBERT SHERRY WATER REVIEW Approved
04/06/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE LAST APPROVED SITE AND FLOOR PLANS BY THE CITY OF TUCSON.
2. PROVIDE EXIT SIGNAGE AND EMERGENCY EGRESS ILLUMINATION AT THE NEW EXIT AND EXIT DISCHARGE.
3. PROVIDE A CODE ANALYSIS WHICH INCLUDES THE NEW AREA AND OCCUPANT LOAD.
4. PROVIDE A DETAILED BREAKDOWN ON THE PLANS OF THE COSTS SPENT UPGRADING ACCESSIBILTIY TO ENSURE THAT 20% OF THE CONSTRUCTION COSTS HAVE BEEN SPENT UPGRADING ACCESSIBILITY.
5. PROVIDE DETAILED INFORMATION REGARDING THE ACCESSIBILITY OF THE PATH OF EGRESS AT THE NEW EXIT AND EXIT DISCHARGE.
6. PROVIDE A WALL SECTION/DETAIL OF THE INFILLED WALLS.
7. PROVIDE A DETAIL/SECTION OF THE NEW TRANSACTION COUNTER/WINDOW TO ENSURE COMPLIANCE WITH ANSI 117.1-2003.
8. PROVIDE HARDWARE INFORMATION TO VERIFY EGRESS COMPLIANCE.
04/06/2007 ANY ENGINEERING REVIEW Approved
04/06/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/27/2007 DROBEY1 WWM REVIEW Needs Review
07/27/2007 DROBEY1 ZONING REVIEW Needs Review
07/27/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/27/2007 DELMA ROBEY APPROVAL SHELF Completed
07/27/2007 DELMA ROBEY OUT TO CUSTOMER Completed
07/27/2007 DELMA ROBEY REJECT SHELF Completed