Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM01426
Parcel: 133170630

Address:
350 N WILMOT RD

Review Status: Completed

Review Details: OTHER

Permit Number - T07CM01426
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM01426 4/16/07

1. Provide TEP Available Fault Current, fault calculations, and fault current rating of equipment.
2. Provide overcurrent protection for the GFCI at the panel.
3. Provide service disconnecting means per NEC 230.70.
4. Provide overload protection for service conductors. Reference NEC 230.90.
5. Grounding Electrode Conductor between the service disconnect and the first ground rod shall be sized at #4. Reference NEC Table 250.66.
6. Please change the routing of the Equipment Grounding Conductor from underground via the ground rods to be installed inside of the PVC to the trailer.
7. Clarify the application of NEC 250.32 after Comment #6 above has been satisfied.