Permit Number - T07CM01424
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/11/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
04/11/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide calculations demonstrating adequate ventilation. Reference Section 401.2, IMC 2003.
04/11/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the water heater and water isometric details.
2. Show the backflow protection devices for the foot spas.
3. Resolve the question of the vent sizes per Section 904.1, UPC 2003.
4. Correct the fixture unit schedule.
04/16/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
04/16/2007 DROBEY1 WWM REVIEW Needs Review
04/16/2007 DROBEY1 FIRE REVIEW Needs Review