Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM01409
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/03/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 05/21/2007 | CHRIS KIEL (WILDAN) | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PLEASE COORDINATE THE STRUCTURAL CALCULATIONS WITHIN THE CALCULATIONS AND WITH THE PLAN SHEET FOR THE PLATFORM PER SECTION 106.1.1 OF THE 2003 IBC. THE CALCULATIONS SPECIFY #4 REBAR AT 12" EACH WAY, BUT THE DETAIL WITHIN THE CALCULATIONS SPECIFY #3 REBAR AT 12" EACH WAY TOP AND BOTTOM. THE PLANS SPECIFY 2-#4 REBAR RUNNING THE 8'-10" DIMENSION WITH "#6 WIRE MECH. 2) PLEASE HAVE THE STRUCTURAL ENGINEER OF RECORD SEAL SHEET P1.0 FOR THE PLATFORM DESIGN IN ACCORDANCE WITH THE REQUIREMENTS OF THE ARIZONA STATE BOARD OF TECHNICIAL REGISTRATION. 3) PLEASE COORDINATE THE DETAIL CALLOUTS BETWEEN DETAIL 205 AND THE PLUMBING WASTE FLOOR PLAN PER SECTION 106.1.1 OF THE 2003 IBC. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/06/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
| 06/06/2007 | SUE REEVES | REJECT SHELF | Completed |