Review Details: COMMERCIAL TI

Permit Number - T07CM01388
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2007 TERRY STEVENS ZONING REVIEW Approved
04/04/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/04/2007 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
04/04/2007 ROBERT SHERRY WATER REVIEW Approved
04/04/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) JUSTIFY ONE HOUR CORRIDOR PER TABLE 1016.1.
04/04/2007 JASON GREEN ENGINEERING REVIEW Approved
04/04/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide the minimum plumbing facilities required by Table 2902.1, IBC 2003, for business occupancy (e.g. drinking fountain)
2. Provide a floor drain in the men's restroom. Reference Section 412.2, UPC 2003.
3. Show that the floor of the restroom slopes toward the floor drain. Reference Section 412.2, UPC 2003.
4. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
5. Include all of the plumbing fixtures (e.g. the urinal) when calculating the total demand and determining pipe sizes. Reference Section 610.1, UPC 2003.
6. Revise water pressure and water pipe sizing calculations to include the flush valve for the urinal (20 fixture units) and use the developed length 250 feet) shown on the calculations. Revise the sizes of the water piping as needed. Reference Section 610.1, UPC 2003.
04/04/2007 MARTIN BROWN FIRE REVIEW Approved
05/01/2007 CAGUILA1 WWM REVIEW Needs Review
05/01/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review