Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T07CM01384
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/18/2007 | MARTIN BROWN | FIRE | REVIEW | Denied | Sht FX101 states an extra hazard group I design area. Indicate where this area is located and what is in this area. Indicate design density for high piled storage. Include commodity classification, storage height, rack height, and all other relevant details for determining required sprinkler flow. Sliding gate (sht. Cl101, note 6) needs to maintain 20' unobstructed access. A fire department lock box will be required. Please show location. Please confirm flow data obtained from Tucson Airport Fire Department and indicate location of hydrants used for flow test. |
| 04/19/2007 | TERRY STEVENS | ZONING | REVIEW | Passed | |
| 05/23/2007 | JASON GREEN | ENGINEERING | REVIEW | Needs Review | Grading plan and FUP required prior to building plan approval. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/06/2007 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 06/06/2007 | SUE REEVES | REJECT SHELF | Completed |