06/01/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM01375 6/1/07

1. AC-2 appears to have 2568 VA per phase, not 2288. Please remove the "*" from the designation on the panel schedule, for this does NOT include 25% for largest motor.
2. AC-4, if it is to be counted as the largest motor, would have 3468 VA per phase, not 2288.
3. AC-1 and AC-3 appear to have 2064 VA per phase, not 1872. Please remove the "*" from the designations on the panel schedule, for this does NOT include 25% for largest motor.
4. Provide fuse size for ACs, or simply size the circuit breaker according to the Mechanical Equipment Schedule.
5. Ampacity of #8 conductor is only 50A, which would not be protected by a 70A CB. Typical for all AC circuits.
06/01/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved