| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/01/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM01375 6/1/07 1. AC-2 appears to have 2568 VA per phase, not 2288. Please remove the "*" from the designation on the panel schedule, for this does NOT include 25% for largest motor. 2. AC-4, if it is to be counted as the largest motor, would have 3468 VA per phase, not 2288. 3. AC-1 and AC-3 appear to have 2064 VA per phase, not 1872. Please remove the "*" from the designations on the panel schedule, for this does NOT include 25% for largest motor. 4. Provide fuse size for ACs, or simply size the circuit breaker according to the Mechanical Equipment Schedule. 5. Ampacity of #8 conductor is only 50A, which would not be protected by a 70A CB. Typical for all AC circuits. |
| 06/01/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/05/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |