Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
04/20/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
04/20/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
04/26/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T07CM01375 4/19/07

1. AC-1 and AC-2 are to be single phase per the Mechanical Equipment Schedule. Electrical provides 3-pole breaker. Coordinate with Mechanical and clarify.
2. Electrical panel is a single phase 120/240 panel, and as such does not accommodate a 3-pole CB.
3. Mechanical calls for 208V equipment. This is a 240V panel. Coordinate with Mechanical and clarify.
04/27/2007 JOHN WILLIAMS COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed