Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM01375
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/20/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/20/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 04/20/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 04/26/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T07CM01375 4/19/07 1. AC-1 and AC-2 are to be single phase per the Mechanical Equipment Schedule. Electrical provides 3-pole breaker. Coordinate with Mechanical and clarify. 2. Electrical panel is a single phase 120/240 panel, and as such does not accommodate a 3-pole CB. 3. Mechanical calls for 208V equipment. This is a 240V panel. Coordinate with Mechanical and clarify. |
| 04/27/2007 | JOHN WILLIAMS | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/18/2007 | THAUSER1 | OUT TO CUSTOMER | Completed |