04/19/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM01375 4/19/07

1. AC-1 and AC-2 are to be single phase per the Mechanical Equipment Schedule. Electrical provides 3-phase power. Coordinate with Mechanical and clarify.
2. Account for largest motor on panel schedule.
3. Coordinate with Mechanical Equipment Schedule to include all motor loads in AC units on panel schedule.
4. Front receptacles are on Ckt 1 on Electrical Plan. They are on Ckt 2 on the panel schedule. Please clarify.
5. There are 5 receptacles on Ckt 16, for a total of 900 VA, not 720.
6. It appears that Ckt 19 should have 844 VA, not 720.