Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T07CM01375
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/19/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM01375 4/19/07 1. AC-1 and AC-2 are to be single phase per the Mechanical Equipment Schedule. Electrical provides 3-phase power. Coordinate with Mechanical and clarify. 2. Account for largest motor on panel schedule. 3. Coordinate with Mechanical Equipment Schedule to include all motor loads in AC units on panel schedule. 4. Front receptacles are on Ckt 1 on Electrical Plan. They are on Ckt 2 on the panel schedule. Please clarify. 5. There are 5 receptacles on Ckt 16, for a total of 900 VA, not 720. 6. It appears that Ckt 19 should have 844 VA, not 720. |
| 04/20/2007 | GBONILL1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 04/20/2007 | GBONILL1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 04/20/2007 | GBONILL1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 04/20/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |