Review Date Reviewer's Name Type of Review Description Status Comments
04/17/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate thw water isometric with the plumbing fixture schedule and detail 7/P-1 for pipe sizes and connections to hot water.
2. Provide calculations to show that the specified attachment of the water heater platform is adequate. Clarify to which wall the platform is being attached; the new partition is built with steel studs.
3. Section 414.1, UPC 2003 does not allow the use of the water heater thermostat to limit the water temperature to the public lavatories.
4. Specify the valves to be used for the showers.
5. Note 12 is still in conflict with the plans.
6. Coordinate the size of the cleanouts with the size of the waste pipes.
04/19/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
04/19/2007 DROBEY1 BUILDING-COMMERCIAL REVIEW Needs Review
04/19/2007 DROBEY1 MECHANICAL-COMMERCIAL REVIEW Needs Review
04/19/2007 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review