Permit Number: T07CM01375
Parcel: 133152880

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM01375
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/03/2007 MARTIN BROWN FIRE REVIEW Approved
04/05/2007 JASON GREEN ENGINEERING REVIEW Approved
04/05/2007 STEVE SHIELDS ZONING REVIEW Approved
04/06/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide calculations to show that the common ventilation system is sized in accordance with Section 403.3.2, IMC 2003.
04/06/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. Provide equipment data for the water heater. Reference Section 103.2.3, UPC 2003.
3. Provide water supply isometrics. Reference Section 103.2.3, UPC 2003.
4. Clarify the design for the mounting shelf for the water heater, specifying the manner of connection to the wall structure. Reference Section 310.0, UPC 2003.
5. Provide a watertight pan of corrosion-resistant material under the water heater with a drain to an approved location. Reference Section 508.4, UPC 2003.
6. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference Section 414.1, UPC 2003 and Section 804.3, IECC 2003.
7. Provide shower control valves that comply with the requirements of Section 420.0, UPC 2003.
8. Coordinate plumbing note 12 with the plumbing design.
9. Calculate the water demand using the fixture units shown in Tables 6-4 or A-2. Reference Section 610.3, UPC 2003.
10. Determine the size of the waste water pipes using the fixture units shown in Table 7-3. Reference Section 703.1, UPC 2003.
04/06/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) GYMNASIUMS ARE A-3 OCCUPANCIES. PLEASE ADJUST CODE ANALYSIS TO REFLECT PROPER OCCUPANCY TYPE. REFERENCE IBC SECTION 303.1.1 IF NECESSARY.

2) ADUST SHOWER DOOR SWING SO THEY DO NOT INTERFERE WITH CLEAR FLOOR SPACE FOR RESTROOM DOOR.

3) PROVIDE DOCUMENTATION FOR LAST APPROVED PERMIT.
04/17/2007 ROBERT SHERRY WATER REVIEW Approved
04/17/2007 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review ELECTRICAL NOTES; PHASE A ON PANEL #3 IS SHOWING 27,182 VOLT AMPS, DEVIDED BY 120 VOLTS GIVES 226AMPS. THIS PANEL IS A 200AMP RATED ONLY.
04/17/2007 GERRY KOZIOL WWM REVIEW Approved
04/17/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review