Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T07CM01362
Parcel: 12308002B

Review Status: Completed

Review Details: OTHER

Permit Number - T07CM01362
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/01/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved