Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/01/2007 GERRY KOZIOL WWM REVIEW Approved
05/01/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM01362 4/26/07

1. Apply for overhead waiver for this electrical service.
2. Locate all equipment on the site plan.
3. Address grounding at the service disconnecting means. Reference NEC 250.24 (B).
4. Provide the following note on the plans: "Contractor shall provide TEP available fault current to electrical inspector before final electrical clearance."