Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T07CM01362
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/20/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/01/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 05/01/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM01362 4/26/07 1. Apply for overhead waiver for this electrical service. 2. Locate all equipment on the site plan. 3. Address grounding at the service disconnecting means. Reference NEC 250.24 (B). 4. Provide the following note on the plans: "Contractor shall provide TEP available fault current to electrical inspector before final electrical clearance." |