Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T07CM01362
Parcel: 12308002B

Review Status: Completed

Review Details: OTHER

Permit Number - T07CM01362
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/01/2007 GERRY KOZIOL WWM REVIEW Approved
05/01/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM01362 4/26/07

1. Apply for overhead waiver for this electrical service.
2. Locate all equipment on the site plan.
3. Address grounding at the service disconnecting means. Reference NEC 250.24 (B).
4. Provide the following note on the plans: "Contractor shall provide TEP available fault current to electrical inspector before final electrical clearance."