| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/20/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 05/01/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 05/01/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM01362 4/26/07 1. Apply for overhead waiver for this electrical service. 2. Locate all equipment on the site plan. 3. Address grounding at the service disconnecting means. Reference NEC 250.24 (B). 4. Provide the following note on the plans: "Contractor shall provide TEP available fault current to electrical inspector before final electrical clearance." |