Review Date Reviewer's Name Type of Review Description Status Comments
05/02/2007 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Activity # T07CM01321
Date: 5/7/07

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2003 International Residential Code, 2003 International Energy Conservation Code, and Arizona State amendments to the 2003 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:
All corrections and revisions shall be made on original tracings or finished reproducible set. Pen or pencil corrections on final prints will not be acceptable. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets.

· The City of Tucson has not adopted the 2006 IRC. The 2003 IRC and the 2003 UPC with amendments should be referenced on the plans.

SITE PLAN:
1. Indicate the location of gas, water, electric and sewer or septic line on the property, from property line to building. Provide the location of utility meters.
2. Show the water pipe size from the meter to the building. Show the point of connection for the proposed branch. The pipe must be sized for the calculated load, 2003 UPC 610.1.

FOUNDATION:
1. Provide a landing or floor surface at all exterior doors. A landing must be at least as wide as the door it serves and 36" in the direction of travel, R311.4.3.

ROOFING PLAN:
1. Provide additional note on roofing plan for clarity: 2x6 RAFTERS @ 12" O.C.

SECTIONS - DETAILS:
1. Provide additional information on location of new trusses (Section A).
2. Provide solid 2x blocking between 2x6 rafters at exterior wall.

PLUMBING PLAN:
1. Provide the total fixture unit schedule for the entire property (to include existing fixtures) per 2003 UPC Tables 6-4 and 7-3.
2. Provide the maximum developed length of water line and diameter from the meter using 2003 UPC Table 6-5 assuming 46 to 60psi if the water pipe serves both the existing and proposed fixtures.

MECHANICAL PLAN:
1. Provide heating facilities capable of maintaining a minimum room temperature of 68 degrees…in all habitable rooms, R303.8.
2. Show clothes dryer exhaust vent size and location for venting to exterior, M1501.

ELECTRICAL PLAN:
1. Show locations of smoke detectors, R313. Note that all smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup. When ceiling finish materials are removed in existing construction, existing bedrooms shall be in compliance. When ceiling finish materials are not removed, existing bedrooms shall be equipped with battery operated smoke detectors, R313.1.1.
2. Receptacles shall be installed so that no point along the floor line in any wall space is more than 6 feet…from an outlet in that space, E3801.2.1 (Area: side door to bay window).
3. At least one wall-switch-controlled lighting outlet shall be installed to provide illumination on the exterior side of each outdoor egress door having grade level access R3803.3 (Area: side door).
4. Provide a note indicating only approved outlet boxes shall be used for ceiling fans, E4001.6.

If you have any questions please contact:
City of Tucson Residential Plan Review
Clayton Trevillyan
(520) 837-4913