Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM01287
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/03/2007 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
04/03/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
04/03/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
04/03/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
04/03/2007 | CARL SCHULTZ | FIRE | REVIEW | Approved | |
04/03/2007 | RSHERRY1 | WWM | REVIEW | Passed | |
04/03/2007 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
04/04/2007 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
04/04/2007 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) BREAKROOM WAS REVISED WITHOUT PERMITS. BREAKROOM DOES NOT COMPLY WITH ANSI A117.1 2003. SINCE THIS IS NEW WORK IT SHOULD BE FULLY COMPLIANT. 2) RECEPTION COUNTER IS NEW PLEASE CLARIFY IT IS COMPLIANT WITH ANSI A117.1 2003. |
04/13/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |