Permit Number: T07CM01275
Parcel: 13414020E

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM01275
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/29/2007 JASON GREEN ENGINEERING REVIEW Approved
03/30/2007 DAVE MANN FIRE REVIEW Approved
03/30/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show that the ventilation for the new use complies with the requirements of Section 403.3, IMC 2003.
03/30/2007 CHRISTY FOREMAN ELECTRICAL-COMMERCIAL REVIEW Approved
03/30/2007 ROBERT SHERRY WATER REVIEW Approved
03/30/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PRIVIDE OCCUPANT LOAD PER EXERCIS ROOM TABLE 1004.1.2.
2)CORRECT CODE CHECK AND CODE ANALYSIS FOR SPRINKLERED BLDG.
3)CLARIFY RETAIL? FOR OCCUPANCY TYPE
4) ALL TEXT ON DRAWINGS SHALL BE A MINIMUM OF 1/8".
03/30/2007 RSHERRY1 WWM REVIEW Passed
03/30/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
04/04/2007 CAGUILA1 ZONING REVIEW Needs Review
04/04/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review