Permit Number: T07CM01263
Parcel: 136170060

Review Status: Completed

Review Details: RESIDENTIAL BLDG/ZONING/ENGINE/NPPO

Permit Number - T07CM01263
Review Name: RESIDENTIAL BLDG/ZONING/ENGINE/NPPO
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2007 WILDAN 2ND PARTY REVIEW REVIEW Denied May 17, 2007


City of Tucson Development Services
P.O. Box 27210
Tucson, AZ 85726

RE: Reeves Residence Addition – 2nd REVIEW
CITY OF TUCSON LOG NO. T07CM01263
WILLDAN PROJECT NO. 13881-7046

The second review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IRC, 1997 UAC, and the 2003 UPC. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Chris Kiel.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
SFR N/A V-B 280 No Smoke


GENERAL COMMENTS:
The City of Tucson is on the 2003 code cycle. Please change all references to the current City of Tucson adopted codes. Reference the City of Tucson Submittal Requirements.

ARCHITECTURAL COMMENTS:
Sheet 3
Show calculation of attic ventilation area. Note location of all vents needed to comply or show compliance with an accepted Non-vented Roof Method Details 1-8, Dated 7/18-19/2001 as permitted by Section R104.11, Alternate Methods. Reference IRC Section R806.2. Comment remains. Not addressed.

Annotate on the plans that the weep screed will be a minimum of 4” above the earth and a minimum of 2” above paved surfaces. Reference IRC Section R703.6.2.1. Comment remains. The keynote indicates an incorrect place and the detail is incomplete.

STRUCTURAL COMMENTS:
Sheet 3
Locate and identify brace wall types and locations, along with the appropriate nailing schedule. Reference IRC Section R106.1.1. Comment remains. The nailing schedule is was not provided for the sheer walls.

PLUMBING COMMENTS:
Sheet 4
Show the size of all waste lines, vents, and required clean-outs. Reference City of Tucson Submittal Requirements. Comment remains. Please indicate the size of all new waste lines.

MECHANICAL COMMENTS:
Sheet 4
Show exhaust fan locations and exhaust duct terminations for bathrooms, water closet compartments and similar rooms in lieu of operable windows. Reference IRC Section R303.3. Comment remains. Not addressed.

ELECTRICAL COMMENTS:
Reviewed and accepted.

ENERGY CODE COMMENTS:
Sheet 2
Please submit the required energy code calculations by using the “RES” check program, Chapter 11 of the IRC, or the 2003 IECC, and also annotate on the plans. Reference IRC Section R106.1.1. Comment remains. Not addressed.



Sincerely,

WILLDAN




Chris Kiel, C.B.O., M.C.P.
Building Official

CEK/jk