Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM01255
Parcel: 11309496A

Review Status: Completed

Review Details: RESIDENTIAL BLDG/WWM

Permit Number - T07CM01255
Review Name: RESIDENTIAL BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2007 GERRY KOZIOL WWM REVIEW Approved
05/03/2007 LINHART PETERSEN POERS ASSOC. 2ND PARTY REVIEW REVIEW Denied May 3, 2007 CITY OF TUCSON- FIRST CHECK
Tucson Appl. No. T07CM01255
Bureau Veritas Job No. 01007-161001.046

Mr. Dave Morkert
4750 N Oracle Rd..
Tucson, Arizona 85705


Re: Plan Review: Water St. SFR
Address: 1250 E. Water St.

Dear Mr. Morkert;

Bureau Veritas North America has completed a First review of the following documents on behalf of the City of Tucson:


Plans: Two (2) sets of plans (10 sheets, 1 through 10) no stamps or dates.

Truss Calculations: None provided with this review

Structural Calculations: None provided with this review



These documents were reviewed only for their conformance to the provisions of the 2003 International Building Codes (i.e., State of Arizona and Pima County amended 2003 IRC, 2003 IMC, 2002 NEC and 2003 IPC). Our comments follow on the attached list.

Please submit an itemized response letter and required number of complete and revised documents with all revisions clouded.




Sincerely;
Bureau Veritas



Randy McCoy
ICC Plans Examiner




RMC:skThese documents were reviewed only for their conformance to the provisions of the 2003 International Building Codes, 2003 International Residential codes, (i.e., State of Arizona and Pima County amended 2003 IRC, 2003 IMC, 2002 NEC and 2003 IPC).

Please respond in writing to each comment by marking the attached comment list or creating a response letter. Indicate which detail, specification, or calculation shows the requested information. Your complete and clear responses will expedite the re-check and hopefully, approval of this project. Thank you for your assistance.

These plan review comments are based on building code items only. If site-related comments are applicable to this project, they will be generated by others (e.g., City Engineering, Public Works, Health, etc.).


FRAMING COMMENTS:

Indicate all braced wall panel locations. Specify the method of bracing to be used. A sealed lateral analysis, prepared by an Arizona Registrant, will be required if the bracing does not comply with the conventional provisions. IRC Section R602.

Indicate the size and span of headers and lintels in all bearing and non-bearing walls. Provide manufacturer's span charts for pre-manufactured steel lintels. IRC Sections R602.7 & R606.9.

Show required holddowns, as specified on lateral design or as required for all alternate braced wall panels, on the foundation plan.

PLUMBING COMMENTS:

Note and specify that the shower area walls shall be finished with a nonabsorbent surface to a height of six feet above the floor. IRC Section 307.2.
Specify if appliances and equipment are gas, electric, or propane. Reference location of appliances and equipment.

TRUSS SYSTEMS:

TRUSS SYSTEMS: Trusses can be submitted as a “Deferred Submittal”. However, they must be submitted and approved prior to their fabrication.

Provide complete truss calculations and truss layout plan. Truss designs submitted must include all types and be designed for the loading conditions, span, slope, and spacing designated on the framing plan.
Truss calculations must be signed, dated and sealed by an Engineer who is registered in the State of Arizona.
The seal on the truss calculations shall be dated within the latest adopted IRC.
All truss calculations shall be cross-referenced to the truss layout or the roof and floor framing plans.

MECHANICAL COMMENTS:

Indicate Access clearances and working space around HVAC equipment. IRC Section M1305.
Provide combustion air for all liquid and solid fuel-burning appliances including size, type, and location of openings. 2003 IRC Chapter 17.
Show condensate line and secondary condensate line. 2003 IRC Section M1411.3 and M1411.3.1.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/04/2007 VFLORES1 OUT TO CUSTOMER Completed