Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T07CM01215
Parcel: 115180050

Review Status: Active

Review Details: COMMERCIAL TI

Permit Number - T07CM01215
Review Name: COMMERCIAL TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
03/26/2007 ANY ZONING REVIEW Active
03/26/2007 ANY MECHANICAL-COMMERCIAL REVIEW Active
03/26/2007 ANY ELECTRICAL-COMMERCIAL REVIEW Active
03/26/2007 ANY WATER REVIEW Active
03/26/2007 ANY BUILDING-COMMERCIAL REVIEW Active
03/26/2007 ANY WWM REVIEW Active
03/26/2007 ANY PLUMBING-COMMERCIAL REVIEW Active
03/26/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Active
03/27/2007 PATRICIA GILBERT ENGINEERING REVIEW Needs Review
03/27/2007 DAVE MANN FIRE REVIEW Denied Please add the following automatic sprinkler criteria to the plans:

1. The hazard classification of the occupancy including any special hazards.
2. The design standard to be used.
3. The availability and adequacy of the water supply.
4. The design density and the area of operation.