Permit Number: T07CM01157
Parcel: 137276510

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM01157
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/22/2007 MICHAEL ST. PAUL ZONING REVIEW Approved
03/22/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how recirculation of the HVAC supply air entering the restrooms is prevented from being recirculated. Reference section 403.2.1 (3), IMC 2003.
03/22/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The specified double check valve is not allowed for use with a carbonator; a reduced pressure backflow preventer is required. Reference Table 6-2, UPC 2003.
03/22/2007 ROBERT SHERRY WATER REVIEW Approved
03/22/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Needs Review 1) STRUCTURAL CALCULATIONS ARE REQUIRED FOR NEW FACADE ADDITIONS ADDED TO EXTERIOR BLDG. ARCH ON TOP NEW WIND LOADS. TRELLIS AND AWNINGS.
03/22/2007 GERRY KOZIOL WWM REVIEW Approved
03/22/2007 DAVE MANN FIRE REVIEW Approved
03/22/2007 ANY ENGINEERING REVIEW Approved
03/27/2007 CAGUILA1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
03/27/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review