Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T07CM01134
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/21/2007 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Provide a letter from Tucson Water confirming that the use of a 1-1/2" water meter will be allowed for this project (129 fixture units equates to a demand of 76 GPM) 2. Reduced pressure backflow prevention assemblies are required to be the same size as the water service connection. Reference COT Ordinance 9976, Section 7-76 (d). http://www.tucsonaz.gov/water/docs/backflow-ord.pdf |
| 06/21/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 06/22/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 07/05/2007 | GBONILL1 | ZONING | REVIEW | Needs Review |