Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM01128
Parcel: 12801017J

Address:
1062 S WILMOT RD

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T07CM01128
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2007 DAVE MANN FIRE REVIEW Approved
07/09/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: July 9, 2007
ACTIVITY NUMBER: T07CM01128
PROJECT NAME: Pockets Pool and Pub
PROJECT ADDRESS: 1062 South Wilmot Road
PROJECT REVIEWER: Patricia Gilbert, Engineering Associate

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: SITE PLAN

1. Provide pavement striping and directional signage to depict direction of traffic for the one-way PAAL.

2. Dimension the existing sidewalk that is located within the ROW. DS 2-02.2.1.A.12.

3. Due to the fact there are only two comments an over the counter review is acceptable. Call to schedule a time; Patricia Gilbert at 837-4936.
07/18/2007 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Pockets Pool & Pub - 1062 S. Wilmot Road
T07CM01128
Site Plan (3rd Review)

TRANSMITTAL DATE: July 19, 2007

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC). Based on the expansion calculation provided, code compliance for the expansion only is required.

2. Zoning acknowledges that this violation will be addressed via separate site plan that meets the requirements of D.S. 2-02. After discussions with Zoning Administration this violation will not delay approval of this site plan. For your information the site plan for parcel 128-01-017H will not be approved until the lot splits, recorded in 1997 and 2001 have been processed through the City of Tucson. It appears that a zoning violation has occurred on site. Per current aerial photos parcel 128-01-017H that is part of this site (west parcel) has been graded without a permit. This has been turned into the Department of Neighborhood Resources, T07DV03035.

3. This comment was not fully addressed. Provide the type and size of the existing sign. D.S. 2-02.2.1.A.13 If applicable provide the location, type, size and height of existing and proposed freestanding signage and billboards.

4. The parking calculation provided is incorrect. Under LUC Sec. 3.3.4 Alcoholic Beverage Service, there is no exclusion of the kitchen area allowed. Based on a floor plan provided to the Zoning Administrator, August 7, 2006, the 994 sq. ft. of kitchen is parked as part of the Alcoholic Beverage Service, requiring an additional 20 parking spaces. Also when the square footage listed under the PARKING REQUIREMENTS are added together, Billiards 4470, existing Alcoholic Beverage Service 827, proposed expansion 560, kitchen 994 are totaled (6851) there is a difference of 340 sq. ft from the total square footage listed under LAND USE, clarify. Provide a floor plan with square footage listed for the two uses. The total parking spaces provided is incorrect, due to the existing chain link fence there are thirty (30) parking spaces that are not useable for this project. This said, there are only forty-nine spaces available for this project. D.S. 2-02.2.2.A.4 Provide a vehicle parking space calculation on the plan. Show the existing and proposed required and provided.

5. There is curbing shown running along the south and west property lines. This curbing is not currently on site. Is this proposed? If not proposed remove from plan.

6. Additional comments may be forth coming depending on how each comment has been addressed.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t07cm01128-2nd.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
07/19/2007 STEVE SHIELDS ZONING HC SITE REVIEW Approved
07/20/2007 ANDREW CONNOR LANDSCAPE REVIEW Denied The planting plan and layout calculations will include the locations, size, and name of existing vegetation to remain in place per DS 2-07.2.2.A.1.e. Identify graphically on the site plan all existing plants.
07/23/2007 ANDREW CONNOR NPPO REVIEW Approved
07/30/2007 DROBEY1 PLUMBING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
07/30/2007 DELMA ROBEY APPROVAL SHELF Completed
07/30/2007 DELMA ROBEY OUT TO CUSTOMER Completed
07/30/2007 DELMA ROBEY REJECT SHELF Completed