Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM01074
Parcel: 11901065B

Address:
3301 S 6TH AV

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T07CM01074
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2008 STEVE SHIELDS ZONING REVIEW Approved
06/16/2008 JASON GREEN ENGINEERING REVIEW Approved DATE: June 16, 2008
SUBJECT: 3301 S 6th Avenue Site Plan- 6th Engineering Review
TO: Lance Robinson
LOCATION: T14S R13E Sec25 Ward 5
REVIEWERS: Jason Green, CFM
ACTIVITY: T07CM01074 (Site Plan)


SUMMARY: Engineering Division of Development Services Department has received and reviewed the revised site plan (T07CM01074), Drainage Statement (L.E.A.D.S., Inc., 20AUG07 revised 15JAN08, 08MAY08), and Geotechnical Investigation Report (Foree&Vann, Inc, 23MAY07 and addendum 13NOV07). The Drainage Statement was reviewed for site plan purposes only. Engineering Division recommends approval of the site plan at this time.


1) Review and approval from TDOT Permits and Codes for all improvements within the public right-of-way will be required. A right-of-way use permit application will be required prior to construction. Refer to the following links for TDOT Forms and applications:

a) http://www.tucsonaz.gov/dsd/Forms_Fees___Maps/Applications/applications.html /

b) http://www.dot.ci.tucson.az.us/engineering/pia.php

c) Or contact Thad Harvison at 837-6592 for all additional questions regarding r-o-w.

GRADING PLAN:

2) DS Sec.11-01.2.1: A grading plan permit application (T07BU02153) has been submitted for review and comments will be posted under a separate letter.

3) Please ensure the grading plan is consistent with the Tentative Plat, Site Plan, Drainage Statement, and Geotechnical Report. Grading standards may be accessed at http://www.ci.tucson.az.us/dsd/DevStandsTOC.pdf.

4) Arizona Pollutant Discharge Elimination System (AZPDES) requirements are applicable to this project. Stormwater Pollution Prevention Plans and text addressing stormwater controls for all areas affected by construction activities related to this development have been submitted and will be reviewed with the grading plan submittal.

GENERAL COMMENTS:

If you have any questions, I can be reached at (520) 837-4929.


Jason Green, CFM
Senior Engineer Associate
Engineering Division
COT Development Services