Permit Number: T07CM01071
Parcel: 13216600A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM01071
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/16/2007 TERRY STEVENS ZONING REVIEW Approved
03/16/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
03/16/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM01071 3/16/07

1. Fill in electrical load on Panel P for Ckts 31, 33, and 35.
2. With an additional 18A, or 9% load change, please provide a load calculation for Panel P which includes all loads on all three phases.
3. Provide fault calculations for the new panel.
03/16/2007 ROBERT SHERRY WATER REVIEW Approved
03/16/2007 MARTIN HAEBERLE BUILDING-COMMERCIAL REVIEW Approved
03/16/2007 RSHERRY1 WWM REVIEW Passed
03/16/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
03/16/2007 DAVE MANN FIRE REVIEW Approved
03/16/2007 MARTY DUPONT ADA REVIEW Approved
03/16/2007 SUE REEVES COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/28/2007 ANY ENGINEERING REVIEW Approved