Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM01071
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/16/2007 | TERRY STEVENS | ZONING | REVIEW | Approved | |
03/16/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
03/16/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM01071 3/16/07 1. Fill in electrical load on Panel P for Ckts 31, 33, and 35. 2. With an additional 18A, or 9% load change, please provide a load calculation for Panel P which includes all loads on all three phases. 3. Provide fault calculations for the new panel. |
03/16/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
03/16/2007 | MARTIN HAEBERLE | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/16/2007 | RSHERRY1 | WWM | REVIEW | Passed | |
03/16/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
03/16/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
03/16/2007 | MARTY DUPONT | ADA | REVIEW | Approved | |
03/16/2007 | SUE REEVES | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
03/28/2007 | ANY | ENGINEERING | REVIEW | Approved |