Permit Number: T07CM01003
Parcel: 137052550

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM01003
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/07/2007 WILDAN 2ND PARTY REVIEW REVIEW Denied December 6, 2007

City of Tucson Development Services
201 N. Stone Avenue
Tucson, AZ 85701


RE: 702 WEST LOUISIANA – 2nd REVIEW
CITY OF TUCSON LOG NO. T07CM01003
WILLDAN PROJECT NO. 13881-7063

The second review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all indicated corrections and revisions to the plans must be made, and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2006 IRC, 2003 IMC, 2003 IECC, 2002 NEC codes with local modifications, and the 2003 UPC with State of Arizona Amendments. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Roger Brooks.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
Dwelling N/A V-B 421 No Smoke


ARCHITECTURAL COMMENTS:
Sheet 4
Note and specify a complete roofing system; roofing type, grade of materials and method of installation. Reference IRC Chapter 9. Comment remains.

For thin-coat stucco systems over foam board, note and specify the listing agency’s evaluation report number, system name and manufacturer, and note and specify the vapor barrier. Reference IRC Section 106.1. Comment remains.

Show calculation of attic ventilation area. Note location of all vents needed to comply or show compliance with an accepted Non-vented Roof Method Details 1-8, Dated 7/18-19/2001 as permitted by Section R104.11, Alternate Methods. Reference IRC Section R806.2. Comment remains.

Sheet 5
Indicate all materials used; stucco, concrete block, glass block, roofing system, siding, veneer, etc. Reference IRC Section R703.1. Comment remains.

STRUCTURAL COMMENTS:
Sheet 4
Specify lateral support of trusses. Reference IRC Sections R802.10.1, R106.1.1. Comment remains.

Specify and detail all over-framing. If solid sheathing is used on the lower trusses, provide minimum openings of 22” by 30” for access and ventilation into over-framed areas (>30 SF). If solid sheathing is not used on lower trusses, provide details for bracing of top chord of lower trusses. Reference IRC Section R807.1 Comment remains.
Completely detail all connections and cross-reference to the foundation and framing plans regarding the following: trusses to top plate, sill to slab, hanger types, hold-down locations and types, straps, and nailing. Reference IRC Section R106.1.1. Comment remains.

Please provide full details on how the #4 rebar should be anchored onto the existing concrete slab and the length at the rebar. Reference Section 106.1.1 of the 2006 IRC. Comment remains.

Sheet 7
Note and detail tie straps, framing anchors, and joist hangers by type, size and required attachment to framing members. Reference IRC Section R106.1.1. Comment remains.

Show details for all bearing and critical non-bearing conditions. Reference IRC Section R106.1.1 Comment remains.

Detail all brace wall connections from the foundation to the roof plywood. Reference IRC Section R106.1.1. Comment remains.

PLUMBING COMMENTS:
Sheet 9
Note and specify all piping materials. Reference UPC Section P2608.1. Comment remains.

Show the size of waste lines, vents, and required clean-outs. Reference City of Tucson Submittal Requirements. Comment remains.

Waterline: Provide the total fixture unit demand (based on Tables 6-4 & 7-3 or Tables L-1 & L-2) and the maximum developed length. Reference UPC Section 610. Comment remains.

MECHANICAL COMMENTS:
Sheet 8
Please provide duct sizes of all the new installation. Reference Section 106.1.1 of the 2006 IRC. Comment remains. The size of some branch lines is not indicated.

ELECTRICAL COMMENTS:
Sheet 10
Designate on the plans the location and circuit of all required light fixtures, receptacles, and switches. Provide a panel schedule noting circuit number and size along with a general description. Reference IRC Chapters E38, E39, and City of Tucson Submittal Requirements. Comment remains.

Submit panel schedule showing circuit amps, wire size, panel size, and circuit numbers. Reference IRC Section 3502.2 and City of Tucson Submittal Requirements. Comment remains.

ENERGY CODE COMMENTS:
Sheet 2
Indicate on the plan the “R” values of insulation, as well as the “U” values of the windows, skylights, and doors in compliance with the energy calculations provided or prescriptive requirements of Chapter 11. Reference IRC Section R106.1.1. Comment remains.

Please submit the required energy code calculations by using the “RES” check program, Chapter 11 of the IRC, or the 2003 IECC, and also annotate on the plans. Reference IRC Section R106.1.1. Comment remains.



Sincerely,

WILLDAN




Roger Brooks, C.B.O., V.P.
Building Official

RAB/jk

Final Status

Task End Date Reviewer's Name Type of Review Description
12/21/2007 CINDY AGUILAR OUT TO CUSTOMER Completed
12/21/2007 CINDY AGUILAR REJECT SHELF Completed