Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM01001
Parcel: 11016223A

Address:
5981 E GRANT RD

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T07CM01001
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/20/2007 DAVE MANN FIRE REVIEW Approved
03/23/2007 BETSY COTTLE COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/30/2007 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 03/30/2007.

Site Plan has not been submitted. Review can not be carried out.
04/10/2007 LINHART PETERSEN POERS ASSOC. 2ND PARTY REVIEW REVIEW Denied April 9, 2007 CITY OF TUCSON - FIRST CHECK
Tucson Appl. No. T07CM01001
Bureau Veritas Job No. 01007-161001.034

Bill Gansline
7311 Timble View Way
Tucson, Az


Re: Plan Review: Grant Road Professional Plaza Bld #4- D
Address: 5975 E Gant Road

Dear Mr. Gansline,

Bureau Veritas North America has completed a first review of the following documents on behalf of the City of Tucson:

Plans: Two (2) sets of building plans (60 sheets, A0.1 through S13) sealed by William R Gansline dated March 11, 2007.

Structural Calculations: Two (2) sets.


These documents were reviewed only for their conformance to the provisions of the 2003 International Building Codes (i.e., State of Arizona and Tucson amended 2003 IRC, 2003 IMC, 2002 NEC and 2003 IPC).

Please submit an itemized response letter and required number of complete and revised documents with all revisions clouded.


Sincerely,

Bureau Veritas North America



Shelley Knuffke
ICC Plans Examiner












Sk:tm s:\Tucson\01007-161001.034pc1
enclosures

Re: Stories: 2
Occupancy/Const.: B/ VB
Building Area (sq. ft.): 18,585


A. The following plan review comments are based on the City of Tucson Building Regulations and referred to the 2003 International Building Code.

B. Please respond in writing to each comment by marking the attached comment list or creating a response letter. Indicate which detail, specification, or calculation shows the requested information. Your complete and clear responses will expedite the re-check and hopefully, approval of this project. Thank you for your assistance.

C. These plan review comments are based on building code items only. If site-related comments are applicable to this project, they will be generated by others (e.g., County Engineering, Public Works, Health, etc.).


GENERAL COMMENTS:

The City of Tucson has not yet adopted the 2006 IBC. All code references must be to the 2003 IBC.

Provide specs and details for all steel stairs.




If you have any questions regarding the above comments, please contact Shelley Knuffke at (520) 576-8400 between 8:00 A.M. to 5:00 P.M., M-F.
04/11/2007 GERRY KOZIOL WWM REVIEW Denied 1: shell building
2: no TI's until sewer fees are paid
3: no wastewater plumbing fixture stubouts
4: needs to permit on-site private sewer-needs DEQ review & approval if over 3000 gal/day- needs to construct HCS(ww 5th floor records couldn't locate any exsisting 8" public HCS)-needs copy of on-site private sewer for base map update.
04/16/2007 ROBERT SHERRY WATER REVIEW Denied 1. Provide a site plan showing the location of the water meter and the backflow assembly.
2. Provide a letter from Tucson Water confirming that the use of a 1" water meter will be allowed for this project (250 fixture units equates to a demand of 100 GPM (flush valve)).
04/18/2007 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Grant Road Professional Plaza
T07CM00998, T07CM00999, T07CM01000 & T07CM01001
Building Plan (1st Review)

TRANSMITTAL DATE: April 18, 2007

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved Development/Tentative Plat.

3. A site card with DSD approvals by Fire, Zoning, Handi-cap, Engineering, and Landscape/NPPO including the approved development plan stamped for site plan approval and signatures is required before the building plan can be approved by Zoning. Two copies of the approved site/development plan, landscape and NPPO plans are to be submitted with the building plans packet for processing and approval as a site plan. No fees are involved in re-stamping the development/tentative plat plans as an approved site plan. The development plan may be walked through for stamps and site card sign off. Submit the following: two copies of the stamped approved development/tentative plat, landscape and NPPO plans must be included with the site plans packet processed together for site approval.

4. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.


If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\grading\t07cm00998.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents

Final Status

Task End Date Reviewer's Name Type of Review Description
05/16/2007 CINDY AGUILAR OUT TO CUSTOMER Completed
05/16/2007 SUE REEVES REJECT SHELF Completed