Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T07CM01000
Parcel: 11016223A

Address:
5983 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM01000
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2007 BUREAU VERITAS 2ND PARTY REVIEW REVIEW Approved
07/03/2007 ROBERT SHERRY WATER REVIEW Denied 1. Comment not addressed. Provide a site plan showing the location of the water meter and the backflow assembly.
2. A 2" water meter is appropriate for a maximum demand of 80 GPM or less. Revise the design appropriately.
07/12/2007 GERRY KOZIOL WWM REVIEW Approved
07/18/2007 TERRY STEVENS ZONING REVIEW Denied see comments for T07CM00998
07/27/2007 LOREN MAKUS ENGINEERING REVIEW Denied Approved site plan must be provided for building plan approval.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/06/2007 SUE REEVES OUT TO CUSTOMER Completed
08/06/2007 SUE REEVES REJECT SHELF Completed