Permit Number: T07CM00999
Parcel: 11016223A

Address:
5979 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM00999
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/27/2007 BUREAU VERITAS 2ND PARTY REVIEW REVIEW Approved
07/03/2007 ROBERT SHERRY WATER REVIEW Denied 1. Comment not addressed. Provide a site plan showing the location of the water meter and the backflow assembly.
2. A 2" water meter is appropriate for a maximum demand of 80 GPM or less. Revise the design appropriately.
07/14/2007 GERRY KOZIOL WWM REVIEW Approved
07/18/2007 TERRY STEVENS ZONING REVIEW Denied see comments for T07CM00998
07/27/2007 LOREN MAKUS ENGINEERING REVIEW Denied Approved site plan must be provided for building plan approval.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/06/2007 SUE REEVES OUT TO CUSTOMER Completed
08/06/2007 SUE REEVES REJECT SHELF Completed