Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL TI
Permit Number - T07CM00955
Review Name: COMMERCIAL TI
Review Status: Active
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/08/2007 | ANY | ZONING | REVIEW | Active | |
03/08/2007 | ANY | WWM | REVIEW | Active | |
03/08/2007 | ANY | BUILDING-COMMERCIAL | REVIEW | Active | |
03/08/2007 | ANY | ENGINEERING | REVIEW | Approved | |
03/08/2007 | ANY | FIRE | REVIEW | Active | |
03/08/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Active | |
03/09/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide mechanical plan. 2. Revise font to a minimum of 1/8", all upper case. |
03/09/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM00955 3/8/07 Provide documentation sufficient to demonstrate that all electrical systems and equipment have been permitted. This may be done by providing a copy of the approved and permitted plans, and referencing such plan set on the plans currently being reviewed. If the above is not possible, electrical plans will have to be generated in accordance with currently enforceable codes and submitted for review, with all electrical systems and equipment being considered as new. |
03/09/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
03/09/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed |