Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T07CM00955
Parcel: 12501028A

Review Status: Active

Review Details: COMMERCIAL TI

Permit Number - T07CM00955
Review Name: COMMERCIAL TI
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
03/08/2007 ANY ZONING REVIEW Active
03/08/2007 ANY WWM REVIEW Active
03/08/2007 ANY BUILDING-COMMERCIAL REVIEW Active
03/08/2007 ANY ENGINEERING REVIEW Approved
03/08/2007 ANY FIRE REVIEW Active
03/08/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Active
03/09/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide mechanical plan.
2. Revise font to a minimum of 1/8", all upper case.
03/09/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM00955 3/8/07

Provide documentation sufficient to demonstrate that all electrical systems and equipment have been permitted. This may be done by providing a copy of the approved and permitted plans, and referencing such plan set on the plans currently being reviewed.

If the above is not possible, electrical plans will have to be generated in accordance with currently enforceable codes and submitted for review, with all electrical systems and equipment being considered as new.
03/09/2007 ROBERT SHERRY WATER REVIEW Approved
03/09/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed