Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T07CM00904
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/09/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/09/2007 | DAVE MANN | FIRE | REVIEW | Denied | The two front exits from the dining/bar area are not 1/3 of the diagonal distance apart when the restrooms are consided. See IFC Section 1014.2.1. The rear exit cannot be considered for the seating area because it goes through the kitchen. |
| 05/10/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 05/10/2007 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/10/2007 | VFLORES1 | OUT TO CUSTOMER | Completed |