Permit Number: T07CM00880
Parcel: 123151110

Address:
1414 N 1ST AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00880
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2007 DAVE MANN FIRE REVIEW Denied Canopy in SE corner is too close to property line. A fire wall is required Chapters 7 of the IBC and IFC.

Art studios are not gernerally F-2. Justify oocupant load and exiting. If sales are allowed Group should be M.
05/15/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Outdoor lighting on Ckt H-15 appears to total 2128VA, not 1275VA. Reference Outdoor Lighting Calculation. This would result in over 22A on the 20A circuit, even before considering continuous loading.
2. Provide cut sheets for the exterior under-canopy lighting fixtures.
3. On the Outdoor Lighting Calculation, if Option 2 is taken, 300,000 lumens per acre are allowed, not 200,000.
4. On the Outdoor Lighting Calculation, (0.23) (200,000) = 46,000, not 460,000.
5. On the Outdoor Lighting Calculation, limit on unshielded component is limited to 12,000 lumens per acre, not 200,000.
6. General Note I on Sheet 01 E is inconsistent with the Outdoor Lighting Calculation.
7. The rooftop receptacle on A-16 on the Power Plan appears to be intended for H-16.
8. When F1 is checked, the result is 32,018A for I1, not 31734A. This increases the values of I2-I9. Ratings for I3, I5 and I6 appear to be greater that the ratings at their respective panels.
05/16/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 5-21-07
ACTIVITY NUMBER: T07CM00880
PROJECT NAME: NUWAY STUDIOS
PROJECT ADDRESS: 1414 N. 1ST AVE.
ARCHITECT / ENGINEER: CHRISTOPHER TRUMBLE
PROJECT REVIEWER: LEERAY HANLY


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 520-909-5154 OR EMAIL AT LEERAY.HANLY@TUCSONAZ.GOV IF YOU CARE TO DISCUSS.


1) CLARIFY/JUSTIFY UNPROTECTED OPENINGS PER TABLE 704.8 ALONG SOUTH AND EAST PROPERTY LINES.

2) PROVIDE DETAILS FOR INFILL PER KEYNOT 06 PP A01.00

3) COMMON ROOM AT EAST END OF HALL TO BE ACCESSIBLE PER ANSI 117.1. PLEASE PROVIDE REQUIRED CLEAR FLOOR SPACES AND 34" MAX SINK HEIGHT.

4) PROVIDE DETAILS FOR RESTROOMS PER ANSI 117.1 SECTION 604 INDICATING CORRECT CLEARANCES FOR TOILETS, SINKS, GRAB BAR HEIGHTS, LOCATION OF CONTROLS, DISPENSERS, ETC.

5) WHAT DO HEXAGON KEYNOTE REFERENCES ON PP A08.OO REFERENCE?

6) CLARIFY PROTECTION OF C2 COLUMNS ON PP S2.00 PER TABLE 601 OF IBC. F2 OCCUPANCY REQUIRES 1 HOUR PROTECTION.

7) I DON'T UNDERSTAND KEYNOTE 7 PP S3.00. WHAT INDICATED BAYS?

8) REFERENCE DETAIL 202 PP S5.00 WHAT SIZE IS CONNECTOR 3x?x WHAT GAUGE?

9) INLINE SUPPLY FAN SUPPORT REFERENCED IN DETAIL 101 PP M02.00 DOES NOT HAVE AN ASSOCIATED STRUCTURAL DETAIL.

10) DIRECTIONAL EMERGENCY EXIT LIGHT REQUIRED AT CORRIDOR INTERSECTION.
05/21/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the basis of the ASHRAE 62-1-2004 ventilation calculations and if the default occupant densities and combined outdoor air rates are not being used, provide justification for the ventilation of the space. Reference Section 403.2, IMC 2003, as amended by the City of Tucson.
2. Provide the structural detail referenced in detail 101/02.00M. Reference Section 106.3.1, IMC 2003.
3. Clarify the location of EF-2, it appears to be located inside of a partition. Reference Section 106.3.1, IMC 2003.
05/21/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
05/21/2007 ROBERT SHERRY WATER REVIEW Approved
05/22/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
05/25/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied An approved site plan is required prior to building plan approval.
05/29/2007 HEATHER THRALL ZONING REVIEW Denied Until the site plan is approved, zoning is not able to approve the tenant improvement.
06/05/2007 GERRY KOZIOL WWM REVIEW Denied needs 8th floor credit evaluation

Final Status

Task End Date Reviewer's Name Type of Review Description
06/13/2007 THAUSER1 OUT TO CUSTOMER Completed
06/13/2007 SUE REEVES REJECT SHELF Completed