Review Date Reviewer's Name Type of Review Description Status Comments
03/06/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM00856 3/6/07

Condenser Electrical calls for 19.1 MCA and 30 MOCP on Sheet M2.1. Is 30.6 A and 40 ACB on Electrical Panel Schedule. Please coordinate with Mechanical and clarify.
03/06/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
2. Provide calculations demonstrating adequate ventilation. Reference Section 401.2, IMC 2003.