Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T07CM00856
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/06/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM00856 3/6/07 Condenser Electrical calls for 19.1 MCA and 30 MOCP on Sheet M2.1. Is 30.6 A and 40 ACB on Electrical Panel Schedule. Please coordinate with Mechanical and clarify. |
03/06/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 2. Provide calculations demonstrating adequate ventilation. Reference Section 401.2, IMC 2003. |