Permit Number: T07CM00827
Parcel: 113100050

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00827
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
04/27/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide listing information for the new smoker. Reference Section 106.3.1, IMC 2003.
2. Provide a Type I hood for the smoker.
3. Maintain an 18" clearance between the smoker and combustible materials (e.g. FRP wall coverings).
4. Provide information on the construction of the smoke evacuator duct and its penetration of the roof/ceiling assembly. (Also, why is it shown as 12" on the drawing but 10" on the manufacturer's literature?)
04/27/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Clarify the scope of plumbing work - Sheet K-1 indicates much more work than the plumbing plan.
04/27/2007 ROBERT SHERRY WATER REVIEW Approved
05/01/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) STRUCTURAL CALCULATIONS SHALL BE PROVIDED FOR EXHAUST HOOD
05/23/2007 VFLORES1 WWM REVIEW Needs Review
05/23/2007 VFLORES1 ZONING REVIEW Needs Review
05/23/2007 VFLORES1 ENGINEERING REVIEW Needs Review
05/23/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
05/23/2007 VFLORES1 FIRE REVIEW Needs Review