Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM00827
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/27/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 04/27/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide listing information for the new smoker. Reference Section 106.3.1, IMC 2003. 2. Provide a Type I hood for the smoker. 3. Maintain an 18" clearance between the smoker and combustible materials (e.g. FRP wall coverings). 4. Provide information on the construction of the smoke evacuator duct and its penetration of the roof/ceiling assembly. (Also, why is it shown as 12" on the drawing but 10" on the manufacturer's literature?) |
| 04/27/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Clarify the scope of plumbing work - Sheet K-1 indicates much more work than the plumbing plan. |
| 04/27/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/01/2007 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) STRUCTURAL CALCULATIONS SHALL BE PROVIDED FOR EXHAUST HOOD |
| 05/23/2007 | VFLORES1 | WWM | REVIEW | Needs Review | |
| 05/23/2007 | VFLORES1 | ZONING | REVIEW | Needs Review | |
| 05/23/2007 | VFLORES1 | ENGINEERING | REVIEW | Needs Review | |
| 05/23/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 05/23/2007 | VFLORES1 | FIRE | REVIEW | Needs Review |