Review Details: COMMERCIAL TI

Permit Number - T07CM00827
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/20/2007 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) OCCUPANT LOAD RO LOBBY AREA NEEDS TO BE CALCULATED AT 1 PERSON FOR 5 SQ. FT, FIXED SEATING, OR 1 PERSON PER 15 SQ. FT FOR TABLES AND CHAIRS.
04/20/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide listing information and the manufacturer's installation instructions for the new smoker. Reference Section 106.3.1, IMC 2003.
04/20/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the size of the natural gas line serving the AC unit, smoker, and the unit heater per Table 12-7, UPC 2003 or provide calculations to justify the size of the pipe.
04/23/2007 MARTIN BROWN FIRE REVIEW Denied Provide hood and suppression system for smoker. Provide listing information and the manufacturer's installation instructions for the new smoker.
04/27/2007 DROBEY1 ZONING REVIEW Needs Review
04/27/2007 DROBEY1 WWM REVIEW Needs Review
04/27/2007 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
04/27/2007 DROBEY1 ENGINEERING REVIEW Needs Review
04/27/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review