Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM00827
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/20/2007 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) OCCUPANT LOAD RO LOBBY AREA NEEDS TO BE CALCULATED AT 1 PERSON FOR 5 SQ. FT, FIXED SEATING, OR 1 PERSON PER 15 SQ. FT FOR TABLES AND CHAIRS. |
04/20/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide listing information and the manufacturer's installation instructions for the new smoker. Reference Section 106.3.1, IMC 2003. |
04/20/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the size of the natural gas line serving the AC unit, smoker, and the unit heater per Table 12-7, UPC 2003 or provide calculations to justify the size of the pipe. |
04/23/2007 | MARTIN BROWN | FIRE | REVIEW | Denied | Provide hood and suppression system for smoker. Provide listing information and the manufacturer's installation instructions for the new smoker. |
04/27/2007 | DROBEY1 | ZONING | REVIEW | Needs Review | |
04/27/2007 | DROBEY1 | WWM | REVIEW | Needs Review | |
04/27/2007 | DROBEY1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
04/27/2007 | DROBEY1 | ENGINEERING | REVIEW | Needs Review | |
04/27/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/27/2007 | DELMA ROBEY | OUT TO CUSTOMER | Completed |