Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T07CM00827
Parcel: 113100050

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T07CM00827
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/02/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show that the existing gas piping is adequate for the replacement gas-fired cooking appliances.
2. Clarify if the new smoker is electric or gas-fired.
3. Clarify if the ice maker new or existing.
03/02/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide listing information and the manufacturer's installation instructions for the new smoker. Reference Section 106.3.1, IMC 2003.
2. Provide capacity and listing information for the new walk-in refrigerator.
03/02/2007 ROBERT SHERRY WATER REVIEW Approved
03/05/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE CODE ANALYSIS FOR SEPARATED OR NON SEPARATED USE.

2) JUSTIFY RESTROOM FIXTURE COUNT. CHAPTER 29 OF IBC REQUIRES SEPARATE FACILITIES FOR MEN AND WOMEN.

3) ACCESSIBLE ROUTE REQUIRED TO RESTROOM. ROUTE MAY NOT GO THROUGH WORK AREAS.

4) RESTROOM DOOR IS HINDERED BY SIDE EXIT DOOR. DOOR SWING MAY NOT INTERFERE WITH CLEAR FLOOR SPACE REQUIRED BY ANSI 117.1
03/05/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied Provide electrical plans.
04/20/2007 VFLORES1 WWM REVIEW Needs Review
04/20/2007 VFLORES1 ZONING REVIEW Needs Review
04/20/2007 VFLORES1 ENGINEERING REVIEW Needs Review
04/20/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
04/20/2007 VFLORES1 FIRE REVIEW Needs Review