Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM00827
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/02/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show that the existing gas piping is adequate for the replacement gas-fired cooking appliances. 2. Clarify if the new smoker is electric or gas-fired. 3. Clarify if the ice maker new or existing. |
03/02/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide listing information and the manufacturer's installation instructions for the new smoker. Reference Section 106.3.1, IMC 2003. 2. Provide capacity and listing information for the new walk-in refrigerator. |
03/02/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
03/05/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE CODE ANALYSIS FOR SEPARATED OR NON SEPARATED USE. 2) JUSTIFY RESTROOM FIXTURE COUNT. CHAPTER 29 OF IBC REQUIRES SEPARATE FACILITIES FOR MEN AND WOMEN. 3) ACCESSIBLE ROUTE REQUIRED TO RESTROOM. ROUTE MAY NOT GO THROUGH WORK AREAS. 4) RESTROOM DOOR IS HINDERED BY SIDE EXIT DOOR. DOOR SWING MAY NOT INTERFERE WITH CLEAR FLOOR SPACE REQUIRED BY ANSI 117.1 |
03/05/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Provide electrical plans. |
04/20/2007 | VFLORES1 | WWM | REVIEW | Needs Review | |
04/20/2007 | VFLORES1 | ZONING | REVIEW | Needs Review | |
04/20/2007 | VFLORES1 | ENGINEERING | REVIEW | Needs Review | |
04/20/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
04/20/2007 | VFLORES1 | FIRE | REVIEW | Needs Review |