Permit Number: T07CM00821
Parcel: 12217002B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T07CM00821
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
03/15/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM00821 3/15/07

1. Feeder and service calculations have to count 75VA/linear foot of Track Lighting. Since these tracks are intended to replace the existing overhead lights, they are anticipated to be operated on a continuous basis with the 25% additional demand factor. Reference NEC 220.12 (B).
2. Existing Cond Unit at 26.5 FLA, operated at 240V, would be 3180 VA per phase, not 3048.
3. Carry above corrections through to service calcs to assure that this service will not be overloaded.
03/16/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review