Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Permit Number - T07CM00802
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/09/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/09/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM00802 3/9/07 1. Revise the font size to a minimum of 1/8", all upper case. 2. Provide disconnecting means for the New SP-1. Reference NEC 430 Part IX. 3. Provide location of Panel HPAC. 4. Specify conduit and conductor size and type for SP-1 circuit. |
| 03/09/2007 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
| 03/09/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the font size to a minimum of 1/8", all upper case. 2. Clarify the termination point of the pumped discharge. |
| 03/09/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/19/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 03/19/2007 | CAGUILA1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/19/2007 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |