Permit Number: T07CM00802
Parcel: 13824093E

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T07CM00802
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/09/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
03/09/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM00802 3/9/07

1. Revise the font size to a minimum of 1/8", all upper case.
2. Provide disconnecting means for the New SP-1. Reference NEC 430 Part IX.
3. Provide location of Panel HPAC.
4. Specify conduit and conductor size and type for SP-1 circuit.
03/09/2007 SUZANNE BOHNET ENGINEERING REVIEW Approved
03/09/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size to a minimum of 1/8", all upper case.
2. Clarify the termination point of the pumped discharge.
03/09/2007 MARTIN BROWN FIRE REVIEW Approved
03/19/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
03/19/2007 CAGUILA1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/19/2007 CINDY AGUILAR OUT TO CUSTOMER Completed