Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM00795
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/01/2007 | TERRY STEVENS | ZONING | REVIEW | Approved | |
03/01/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
03/01/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
03/01/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
03/01/2007 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
03/01/2007 | GERRY KOZIOL | WWM | REVIEW | Approved | |
03/01/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
03/01/2007 | SUZANNE BOHNET | ENGINEERING | REVIEW | Approved | |
03/01/2007 | MARTIN BROWN | FIRE | REVIEW | Approved | |
03/01/2007 | SUE REEVES | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |