Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM00783
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/02/2007 | VFLORES1 | ZONING | REVIEW | Needs Review | |
| 11/02/2007 | VFLORES1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 11/02/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM00783 11/2/07 1. Please provide fault calculations, and fault current rating of new panel. 2. Symbol for receptacle is for that of 120V, not 208V line-to-line. 3. Provide an electrical circuit for the new exhaust fans. 4. It appears that the overcurrent protection for the water heater is undersized. Reference NEC 422.11 (E) (3). 5. The 60A CB does not protect the water heater circuit at its ampacity. 6. Water heater is specified as 240V on Sheet E-1, and powered at 208V. 7. Provide the size of the Grounding Electrode Conductor. |
| 11/02/2007 | VFLORES1 | WATER | REVIEW | Needs Review | |
| 11/02/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/02/2007 | VFLORES1 | WWM | REVIEW | Needs Review | |
| 11/02/2007 | VFLORES1 | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 11/02/2007 | VFLORES1 | ENGINEERING | REVIEW | Needs Review | |
| 11/02/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 11/02/2007 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |