Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2007 VFLORES1 ZONING REVIEW Needs Review
11/02/2007 VFLORES1 MECHANICAL-COMMERCIAL REVIEW Needs Review
11/02/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM00783 11/2/07

1. Please provide fault calculations, and fault current rating of new panel.
2. Symbol for receptacle is for that of 120V, not 208V line-to-line.
3. Provide an electrical circuit for the new exhaust fans.
4. It appears that the overcurrent protection for the water heater is undersized. Reference NEC 422.11 (E) (3).
5. The 60A CB does not protect the water heater circuit at its ampacity.
6. Water heater is specified as 240V on Sheet E-1, and powered at 208V.
7. Provide the size of the Grounding Electrode Conductor.
11/02/2007 VFLORES1 WATER REVIEW Needs Review
11/02/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
11/02/2007 VFLORES1 WWM REVIEW Needs Review
11/02/2007 VFLORES1 PLUMBING-COMMERCIAL REVIEW Needs Review
11/02/2007 VFLORES1 ENGINEERING REVIEW Needs Review
11/02/2007 DAVE MANN FIRE REVIEW Approved
11/02/2007 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review