Permit Number: T07CM00782
Parcel: 12103074A

Address:
5801 E PIMA ST

Review Status: Completed

Review Details: REVISION - - 2ND

Permit Number - T07CM00782
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/27/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/27/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T07CM00782 9/27/07

1. Add 25% of largest motor per NEC 220.14 (C), 430.24, 440.7.
2. Subtotal, without the addition of 25% per Comment 1, is 40,780, not 36,784.
3. Demonstrate that no phase is overloaded.