Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T07CM00782
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/27/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 09/27/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T07CM00782 9/27/07 1. Add 25% of largest motor per NEC 220.14 (C), 430.24, 440.7. 2. Subtotal, without the addition of 25% per Comment 1, is 40,780, not 36,784. 3. Demonstrate that no phase is overloaded. |