Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T07CM00778
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/05/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | t07cm00778 10/05/07 1. Fault calculations refer to TEP standards. The only such standard would be SR-510, which states that for overhead commercial services, TEP must be contacted for available fault current. 2. The use of a series rating in this case implies a multi-tiered rating, beginning with the 200 A fuse, the Main on Panel K, breakers in Panel K, and then breakers in Panel A. This is not available commercially. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/10/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |