Permit Number: T07CM00778
Parcel: 124020450

Address:
1621 E 1ST ST

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T07CM00778
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t07cm00778 10/05/07

1. Fault calculations refer to TEP standards. The only such standard would be SR-510, which states that for overhead commercial services, TEP must be contacted for available fault current.
2. The use of a series rating in this case implies a multi-tiered rating, beginning with the 200 A fuse, the Main on Panel K, breakers in Panel K, and then breakers in Panel A. This is not available commercially.