Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2007 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 5-15-07
ACTIVITY NUMBER: T07CM00729
PROJECT NAME: ARIZONA CABINET
PROJECT ADDRESS: 2227 S. MISSION RD.
ARCHITECT / ENGINEER: M. TALAVERA
PROJECT REVIEWER: LEERAY


TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 520-837-4908 OR EMAIL AT LEERAY.HANLY@TUCSONAZ.GOV IF YOU CARE TO DISCUSS.

1) PLEASE PROVIDE CODE ANALYSIS FOR ENTIRE BUILDING.

2) PLEASE SUBMIT PLANS WITH MINIMUM 1/8" FONT SIZE FOR DETAIL PAGES.

3) THERE ARE MULTIPLE REFERENCES TO THE INTERNATIONAL RESIDENTIAL CODE. YOU MUST USE THE INTERNATIONAL BUILDING CODE FOR COMMERCIAL STRUCTURAL APPLICATIONS.

4) CLARIFY WHAT WILL BE STORED IN NEW AREA. CLARIFY OCCUPANCY OF NEW STORAGE AREA (S,F OR H)

5) PROVIDE DETAILS FOR LINTELS AT MASONRY OPENINGS.

6) JUSTIFY PER IBC TABLE 602 THE FIRE RESISTANCE OF BEARING WALL LESS THAN 10' FROM PROPERTY LINE. REF KEYNOTE 8,9 PP4 AND DETAIL 4 PP 3.

7) INDICATE THAT BUILDING IS FULLY ACCESSIBLE OR CLARIFY COMPLIANCE WITH SECTION 3409 OF THE IBC.
05/14/2007 DAVE MANN FIRE REVIEW Approved
05/17/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
05/17/2007 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide calculations demonstrating adequate ventilation. Reference Section 401.2, IMC 2003.
2. Show that this addition is exempt from the scope of Section 101.2, IECC 2003 or demonstrate energy code compliance using calculations based on the current code. Reference Section 101.4, International Energy Conservation Code 2003.
05/17/2007 ROBERT SHERRY WATER REVIEW Approved
05/24/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1) Registrant shall seal plans. Reference Rules of the Arizona Board of Technical Registration R4-30-304. Use of Seals, http://www.azsos.gov/public_services/Title_04/4-30.htm#ARTICLE%203.%20REGULATORY%20PROVISIONS.
2) This installation shall be designed in compliance with the National Electrical Code, not the IRC.
3) Demonstrate compliance with the 2003 IECC.
4) Identify panel and circuit number for each new electrical load.
5) Provide lighting fixture cut sheets.
6) Provide panel schedule and load calculations.
7) Provide a legend, or key to symbols.
8) Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997.
9) Specify conduit and conductor size and type.
05/29/2007 PATRICIA GILBERT ENGINEERING REVIEW Approved
06/04/2007 STEVE SHIELDS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Arizona Cabinet
T07CM00729
Building Plan (1st Review)

TRANSMITTAL DATE: June 4, 2007

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\grading\t07cm000729.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents
06/14/2007 SUE REEVES COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
06/14/2007 SUE REEVES APPROVAL SHELF Completed
06/14/2007 SUE REEVES OUT TO CUSTOMER Completed