Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T07CM00729
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/14/2007 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON DEVELOPMENT SERVICES STRUCTURAL REVIEW COMMENTS DATE: 5-15-07 ACTIVITY NUMBER: T07CM00729 PROJECT NAME: ARIZONA CABINET PROJECT ADDRESS: 2227 S. MISSION RD. ARCHITECT / ENGINEER: M. TALAVERA PROJECT REVIEWER: LEERAY TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 520-837-4908 OR EMAIL AT LEERAY.HANLY@TUCSONAZ.GOV IF YOU CARE TO DISCUSS. 1) PLEASE PROVIDE CODE ANALYSIS FOR ENTIRE BUILDING. 2) PLEASE SUBMIT PLANS WITH MINIMUM 1/8" FONT SIZE FOR DETAIL PAGES. 3) THERE ARE MULTIPLE REFERENCES TO THE INTERNATIONAL RESIDENTIAL CODE. YOU MUST USE THE INTERNATIONAL BUILDING CODE FOR COMMERCIAL STRUCTURAL APPLICATIONS. 4) CLARIFY WHAT WILL BE STORED IN NEW AREA. CLARIFY OCCUPANCY OF NEW STORAGE AREA (S,F OR H) 5) PROVIDE DETAILS FOR LINTELS AT MASONRY OPENINGS. 6) JUSTIFY PER IBC TABLE 602 THE FIRE RESISTANCE OF BEARING WALL LESS THAN 10' FROM PROPERTY LINE. REF KEYNOTE 8,9 PP4 AND DETAIL 4 PP 3. 7) INDICATE THAT BUILDING IS FULLY ACCESSIBLE OR CLARIFY COMPLIANCE WITH SECTION 3409 OF THE IBC. |
| 05/14/2007 | DAVE MANN | FIRE | REVIEW | Approved | |
| 05/17/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 05/17/2007 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide calculations demonstrating adequate ventilation. Reference Section 401.2, IMC 2003. 2. Show that this addition is exempt from the scope of Section 101.2, IECC 2003 or demonstrate energy code compliance using calculations based on the current code. Reference Section 101.4, International Energy Conservation Code 2003. |
| 05/17/2007 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 05/24/2007 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1) Registrant shall seal plans. Reference Rules of the Arizona Board of Technical Registration R4-30-304. Use of Seals, http://www.azsos.gov/public_services/Title_04/4-30.htm#ARTICLE%203.%20REGULATORY%20PROVISIONS. 2) This installation shall be designed in compliance with the National Electrical Code, not the IRC. 3) Demonstrate compliance with the 2003 IECC. 4) Identify panel and circuit number for each new electrical load. 5) Provide lighting fixture cut sheets. 6) Provide panel schedule and load calculations. 7) Provide a legend, or key to symbols. 8) Revise the font size used on the drawings to a minimum of 1/8-inch (all upper case). Reference Section 302.3, Uniform Administrative Code, 1997. 9) Specify conduit and conductor size and type. |
| 05/29/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Approved | |
| 06/04/2007 | STEVE SHIELDS | ZONING | REVIEW | Denied | DSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Arizona Cabinet T07CM00729 Building Plan (1st Review) TRANSMITTAL DATE: June 4, 2007 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the building plan was in compliance with the approved site plan. Please submit two copies of the approved and stamped site, landscape, and NPPO plans with the next building plan submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved and stamped site plan. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956. C:\planning\grading\t07cm000729.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents |
| 06/14/2007 | SUE REEVES | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/14/2007 | SUE REEVES | APPROVAL SHELF | Completed |
| 06/14/2007 | SUE REEVES | OUT TO CUSTOMER | Completed |